Exhaust Stack and/or Industrial Chimney inspections
Note: There have been new actions to this contract opportunity. To view the most recent action, please click here.
Looking for contract opportunity help?
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
General Information
- Contract Opportunity Type: Sources Sought (Original)
- Original Published Date: Oct 27, 2022 12:05 pm EDT
- Original Response Date: Nov 28, 2022 05:00 pm EST
- Inactive Policy: 15 days after response date
- Original Inactive Date:
- Initiative:
- None
Classification
- Original Set Aside:
- Product Service Code:
- NAICS Code:
- 561790 - Other Services to Buildings and Dwellings
- Place of Performance: Aiken , SC 29808USA
Description
****This is a REQUEST FOR INTEREST ONLY! This request does not constitute a request for proposal, request for quote, or invitation for bid. The intent of this request is to identify potential offerors for mark research purposes only*****
Savannah River Nuclear Solutions, LLC (SRNS), which manages and operates portions of the Savannah River Site (SRS) under a Department of Energy (DOE) prime contract, solicits expressions of interest from potential suppliers who have a strong background in Exhaust Stack and/or Industrial Chimney inspections.
The SRS complex is located approximately 15 miles south of Aiken, South Carolina and is 310 contiguous square miles.
Request for Information (RFI)
Scope Summary:
Provide an internal stack inspection at SRS for an active stack. The stack has a flow rate of 111,121 cfm and exit velocity of 2,220 fpm. The temperature of air flow exiting the stack is approximately room temperature (690-720 Fahrenheit). The stack is 200 feet high.
296-H is comprised of a 183’-8” concrete chimney without stack liner sitting atop a reinforced concrete foundation. The chimney varies in size and thickness from 12’-11 7/8” outer diameter with 10” thickness at its base, reducing down to outer diameter of 11.04’ and 6” thickness at 90 feet, and then maintains 6” thickness while reducing in size to an outer diameter of 9’-0”. The stack foundation is 25’-0” tall in total, with the bottom 4’-0” comprised of a 36’-0” wide octagonal Footing.
1. During the inspection the stack flow rate and velocity can be reduced to 32,360 cfm and the air exiting the stack would be approximately 647.2 ft/min.
2. Potential for radiation contamination on equipment. However – SRNS will have our Radiological Team during planning, and any work being done.
3. Ability to perform work scope by not “touching” stack (i.e. no climbing of the stack, no attaching equipment on the stack, etc.).
4. Provide report and pictures/videos of stack to determine status of structure.
A supplier's response to the RFI does not guarantee they will be selected to participate in the RFP.
Suppliers responding to this RFI shall include evidence of the following:
1. Overview of how the subcontractor intends to perform a non-destructive and/or visual inspection on an active stack with similar specs.
2. Examples of past performance in stack inspection. For example, a report of an inspection that was previously completed.
E-mail response addressing Items 1 and 2 above shall be submitted by 5:00 p.m. est. on 11/28/22 to Barbara McCarty at barbara.mccarty@srs.gov.
Attachments/Links
Contact Information
Contracting Office Address
- 203 LAURENS ST SW
- Aiken , SC 29801
- USA
Primary Point of Contact
- Barbara McCarty
- barbara.mccarty@srs.gov
- Phone Number 8039526119
Secondary Point of Contact
History
- Dec 13, 2022 11:56 pm ESTSources Sought (Updated)
- Oct 31, 2022 07:56 am EDTSources Sought (Updated)
- Oct 27, 2022 12:05 pm EDTSources Sought (Original)