Skip to main content

An official website of the United States government

You have 2 new alerts

500 KVA Liquid Fill Pad Mount Transformer Type

Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information

  • Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
  • Original Published Date: Aug 20, 2024 03:11 pm EDT
  • Original Date Offers Due: Sep 03, 2024 12:00 pm EDT
  • Inactive Policy: 15 days after date offers due
  • Original Inactive Date: Sep 18, 2024
  • Initiative:
    • None

Classification

  • Original Set Aside:
  • Product Service Code: 6120 - TRANSFORMERS: DISTRIBUTION AND POWER STATION
  • NAICS Code:
    • 335311 - Power, Distribution, and Specialty Transformer Manufacturing
  • Place of Performance:
    San Diego , CA
    USA

Description

Product: 500 KVA Liquid Fill Pad Mount Transformer Type, or Equal

MPD Naval Base San Diego is requesting a 500KVA fluid filled 12470-480/277 3Ph Pad mount Transformer 

^HITACHI 500 KVA Liquid Filled Padmounted Transformer Type. 

Padmounted 

HV 12470 Delta LV-480Y/277 3P 60HZ 

Description: 

Type CU/CU 

Padmounted Transformer Fluid Natural Ester Fluid 

Core Grain Oriented Steel Phase 3 Phase 

Frequency 60 Hz 

Average Winding Rise 65 °C Ambient Temperature 30 °C High Voltage 12470 Delta High Voltage Taps +2 -2 2.5%High Voltage BIL 95kV BIL Low Voltage 480Y/277 

Low Voltage BIL 30kV BIL Low Voltage Neutral XO bushing with ground strap 

Feed Configuration Loop feed Color Bell Green (Munsell 7GY 3.29/1.5

Customer Specification NONE Features (included in price): TANK & CABINET 

Dry Nitrogen Blanket 

304L Stainless Steel Transformer (Tank+Base+Cabinetry

6 parking stands 

Full Tank Weather cover Seismic rated transformer design with seismic anchors 

Penta-head cabinet handle bolt SST hardware 

GROUNDING 

2-hole ground pads (1 in HV and 1 in LV) 

BUSHINGS 

Threaded stud LV bushings x 4 Load break inserts 25 kV (dead front) x 6 

ANSI C57.12.34 Fig 9&11 HV 

bushing pattern (minimum

200-amp HV bushing wells x 6 

6-hole NEMA spade terminals x 4 Spade Supports 

ANSI C57.12.26 Fig 3&4a minimum stgrd LV bushing pattern ARRESTERS 

12 kV MCOV 10.20 elbow arrester - 25 kV interface x 3 

FUSES 

Oil retaining valve on bayonet x 3 

Scoop drip shield x 3 

Bayonet expulsion fuse no isolation link x 3 

Oil-immersed partial range current limiting fuse x 3 

Spare current limiting fuses x 3 SWITCHES 

4-position 200-amp T-blade make before break (closed transition) 

MONITORING 

Thermometer w 2 alarm contacts 1 NO & 1 NC each Qualitrol 

167-288-01 p/n 30C6637H01 Pressure Vac Gauge with Bleeder & Contacts 

Schrader valve 

Minco temperature sensor 

Liquid Level Gauge Qualitrol 

032-35E p/n 2810777H01 with one high and one low contact both are 

1 NO & 1.NC 

Large pressure relief device w 

INO & 1NC Contact 208-60F p/n 2B12401H01 

Pressure Relief Valve 

FITTINGS 

Drain valve and sampler MARKINGS 

Three (3) DANGER HIGH VOLTAGE Signs 

Non-PCB label 

UL Listed on Nameplate 

Stainless steel nameplate 

Fuse operation warning label 

"Non-PCB" on Nameplate 

Mr Ouch DANGER label internal OTHER 

9.5" x 17.5" Tank Handhole Cover 24" deep cabinet 

DOE Efficiency (2016

TESTS 

(1918DGA) DGA Before Shipment Six-hour leak test 

Contains less-flammable biodegradable natural ester fluid with no detectable level of PCB, less than 1PPM, at the time of manufacture. 

Contact Information

Contracting Office Address

  • 1800 F St NW Suite 3200
  • Washington , DC 20006
  • USA

Primary Point of Contact

Secondary Point of Contact





History

  • Sep 18, 2024 11:55 pm EDTCombined Synopsis/Solicitation (Original)