Cart Washer:
Cart washer (including service area) must be no longer than 122.5 and fit in a finished wall opening of 124 W x 105 H
Safety features to include chamber illumination, emergency stop and door interlock.
Steam Condensate return
Automatic Floor tilt
Chamber capacity minimum 40x80x106
Removable Debris Screen.
Safety Door Switch.
Spraying System
Obstruction Sensor.
Horizontal Sliding Doors
Interior Lights
Emergency Stop Pushbuttons.
Door Interlock.
Lock/Unlock Key Selector.
Emergency stop cable
Non-recirculated, venting drying system
Integral Exhaust
Drain discharge cool down
Heating System
Process data validation system
Wash phase, Thermal Rinse Phase, HEPA-Filtered Air Drying
Touch-screen panel user interface, minumun dimensions 5.5 x 7.0
PC-based control system to monitor and control washer operations and functions as well as store cycle data.
Pre-programable parameters
Qty. 1, Container and Qty 1, Utensil carts
Bar code scanner
Compatible with Steris Prolystica® Ultra Concentrate HP Neutral Detergent
Standards Applied to meet Performance Requirements and Safety: EN ISO 15883-1:2009/Amd 1:2014, ANSI/AAMI ST15883-1:2009 and CAN/CSA Z15883-1:09:2014.
Cart washer will be provided with a maximum 120 high service clearance from finished floor to structural deck, however within this area there are 3 structural beams present running perpendicular to the direction of operation. The bottom of these structural beams will be at a height of 109-7/8 from finished floor. Cart washer installation and utility connections must be coordinated to account for the presence of these beams.
Cart washer must be packaged and delivered to the site in pieces no larger than 49 x 83 x 121 such that it may be handled and will pass through existing openings
Cart washer must be pit-mounted over a concrete recessed pit of dimensions 78 W x 118 L x 6.75 D
Cart washer shall utilize 1-1/2 NPT high pressure steam @ 80 PSI connection
Cart washer shall utilize 1 NPT condensate return connection.
Cart washer shall utilize 4 outside diameter drain connection to a floor sink in the recessed pit
Cart washer shall utilize a 6 round stainless steel exhaust duct connection
Cart washer shall utilize 1 NPT domestic cold water connection
Cart washer shall utilize 1 NPT domestic hot water connection
Cart washer shall utilize ¾ NPT reverse osmosis water connection
Cart washer shall utilize ½ compressed air connection at 80-120 PSI
Cart washer shall utilize a 480V, 20 amp, 3 phase electrical connection
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Washer Disinfectors:
Qty 3, washer disinfectors
Qty 2, three level manifold racks
Qty 1, two level manifold rack
Condensate return
Maximum dimensions of each unit- 42 W x 38 D x 91 H
The 3 washer disinfectors when installed side-by-side must fit in a finished wall opening of 129 W x 96 H
Each washer disinfector must be packaged and delivered to the site in pieces no larger than 47.5 x 93.5 x 47.5 such that they may be handled and will pass through existing openings
Spray arm system providing entire chamber coverage
Audible warning system with adjustable volume
Color touch screen control system and visual progress indicator
Minimum 10 custom cycles
Obstruction Sensor
Safety lockout features
Door interlock feature
Safety STOP pushbutton(s)
Protocol Printer
Each washer disinfector shall utilize 1/2 NPT high pressure steam @ 80 PSI connection
Each washer disinfector shall utilize 1/2 NPT condensate return connection.
Each washer disinfector shall utilize 1-1/2 outside diameter drain connection to a floor sink beneath the unit
Each washer disinfector shall utilize 1/2 NPT domestic cold water connection with operating flow rate of 10.7 to 14.1 GPM
Each washer disinfector shall utilize 1/2 NPT domestic hot water connection with operating flow rate of 6.8 to 14.1 GPM
Each washer disinfector shall utilize 1/2 NPT reverse osmosis water connection
Each washer disinfector shall utilize 1/8 compressed air connection at 80-125 PSI
Each washer disinfector shall utilize a 480V, 30 amp, 3 phase electrical connection
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Hydrogen Peroxide Sterilizers:
Qty 2, low temperature hydrogen peroxide sterilizers
Maximum dimensions of each unit- 33 W x 38-5/16 D x 72 H
Minimum chamber dimensions of each unit- 17 W x 32.5 D x 15 H
At a minimum sterilizer must be able to processes up to 11 lbs of non-lumened devices in 16 minutes
Delayed start and load conditioning features
Minimum of 4 cycles (selectable)
Moisture check feature to confirm loads are dry
Hands-free chamber access for loading
Low Sterilant notification
Cycle information collection for electronic record management
Touch screen controls
Each hydrogen peroxide sterilizer shall include a power cord, and utilize a 208V, 20 amp, 3 phase GFCI receptacle
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Small Sterilizer:
Qty 1 single door sterilizer
Dimensions of 45 5/8 L x 30 W x 74 ½H
Must fit in a finished wall opening of 28-1/8 W x 74-1/4 H. Accommodate finished wall thickness between 4 and 8 .
Minimum chamber size of 20 x 20 x 38
Minimum Qty 1, rack and Qty 2 shelves
Vertical sliding door
Allow for hands-free loading and unloading
Ability to process up to 3 25lb trays, minimum
Meets current AAMI/AORN guidelines
Must interface with Censitrac
Sterilizers shall have ink on paper printout
Shall have a Dart (Bowie-Dick) and vacuum leak test cycles
Pressure chamber shall have a full jacket
Minimum 12 programmable cycles - gravity and pre-vacuum
Touch screen display
Ability to furnish a duplicate printout of each cycle
Minimum qty 1, loading trolley with one loading rack
Small sterilizer must fit and be operational within a 52 W x 52 D service clearance area.
Small sterilizer shall utilize 1/2 NPT high pressure steam @ 80 PSI connection. Peak steam consumption of 158 LB/HR, average cycle 42 LB max.
Small sterilizer shall utilize 1-1/2 outside diameter drain connection to a floor sink beneath the unit
Small sterilizer shall utilize 1 NPT domestic cold water connection at 30-50 PSI. Peak water consumption of 15 GPM, average cycle 175 GAL max.
Small sterilizer shall utilize a 120V, 20 amp, single phase electrical connection
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Automated Passthrough Window Single Shelf:
Qty 1, Automated Passthrough Window with Single Shelf
Must fit in a finished wall opening of 28-1/4 W x 45-1/4 H. Accommodate finished wall thickness of 4-7/8 .
Minimum service opening : 24 W x 17-1/2 H.
Frame : Aluminum extrusions
Finish : Clear anodized aluminum
Minimum 1/4 Clear tempered glass
Automatically opens and closes
Dual microwave sensor actuation from both interior and exterior side
304 stainless steel shelf
Shelf to extend minimum 4 from window frame on the soiled side, maximum 25 from window frame on the clean side
Provide angled wall supports beneath shelf
Opener shall utilize a 120V, 20 amp, single phase electrical connection
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Automated Passthrough Window Double Shelf:
Qty 2, automated passthrough windows with double shelf
Must fit in a finished wall opening of 28-1/4 W x 45-1/4 H. Accommodate finished wall thicknesses of 4-7/8 and 7-1/4 .
Minimum service opening : 24 W x 17-1/2 H.
Frame : aluminum extrusions
Finish : clear anodized aluminum
Minimum 1/4 Clear tempered glass
Automatically opens and closes
Dual microwave sensor actuation from both interior and exterior side
304 stainless steel shelves
Shelf to extend minimum 4 from window frame on the soiled side, maximum 25 from window frame on the clean side
Provide angled wall supports beneath shelves
Opener shall utilize a 120V, 20 amp, single phase electrical connection
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Rack Return Window:
Qty 1, rack return window for transferring washer disinfector manifold racks between clean and soiled sides of the SPS department.
Overall dimensions 34-3/4 W x 39-11/16 L x 93 H
Minimum interior chamber dimensions 27-1/8 W x 33-1/8 L x 28-9/16 H
Must fit in a rough wall opening of 36-3/8 W x 48-1/2 H. Accommodate finished wall thickness of 4-7/8
Provide wall flanges for finished opening
Minimum Qty 2, auto docking transfer cart adapters
Automated doors to allow handsfree operation
Interlocking doors
Obstruction sensor
Manually operated safety lock/hold open on both doors
Status indicator lighting
Voice communication system to allow operators on each side to communicate
Capable of handling fully loaded racks up to 160 lbs minimum
Unit shall utilize a 120V, 20 amp receptacle
Unit shall utilize 1/8 NPT compressed air connection at 80-100 PSI
Adapter for transfer cart docking
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Sonic Irrigators:
Qty 2, sonic irrigators
Maximum dimensions of each unit- 35 W x 26 D x 44 H
Minimum wash chamber dimensions of each unit- 29.5 W x 14.4 D x 9.3 H
Frequencies shall adjust to compensate for load variations
Unit provides ANSI/AAMI ST 15883-2:2013 4.3 compliant Thermal Disinfection
Minimum reprocess of 20 lumened devices or minimum 44 lbs in every cycle
Internal chemical cupboard for 2 bottles of maximum size 9 W x 8 D x 17 H
Automated dosing and delivery of chemicals
Meets all robotic instrument IFU requirements with automated wash, flush and rinse cycles
Integrated record keeping
Capability to export key cycle parameters
Automated locking lid
Compatible with most common instrument trays used in healthcare settings
Touch screen controls
Maximum noise output of 68 dB @ 1 meter in front of the machine
Each sonic irrigator shall utilize 1-1/2 outside diameter drain connection to a floor sink beneath the unit
Each sonic irrigator shall utilize 1/2 NPT domestic cold water connection with operating flow rate of 3 to 8 GPM
Each sonic irrigator shall utilize 1/2 NPT domestic hot water connection with operating flow rate of 3 to 8 GPM
Each sonic irrigator shall utilize 1/2 NPT reverse osmosis water connection with operating flow rate of 3 to 8 GPM
Each sonic irrigator shall utilize 1/2 compressed air connection at 30-40 PSI
Each sonic irrigator shall utilize a 208V, 35 amp, 3 phase electrical connection
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Scope Station Triple Bay Sinks:
Qty 2, right to left workflow triple bay sinks
Qty 2, left to right workflow triple bay sinks
Each unit must be packaged and delivered to the site in pieces no larger than 132 x 36 x 48 such that they may be handled and will pass through existing openings
Overall maximum unit dimensions 120 W x 28-1/32 D x 52-17/32 T (at max operating height)
Three basins, each with minimum dimensions 30 x 17 x 10"
Stainless Steel Construction
Air and water pistol attachments
Magnetic back splash
Drain system and flex plates
Etched gallon markers in all bays
Must be height adjustable, with minimum working surface height range of 33 to 41
Minimum weight capacity of adjustment lift 562 lbs
Minimum speed of adjustment system 3/8 per second
Must have Pure water faucet
Each unit shall come with a P-trap and utilize a 1-1/2 diameter drain connection.
Each unit shall utilize 1/2 NPSM domestic cold water connection with pressure range of 20 to 44 PSIG
Each unit shall utilize 1/2 NPSM domestic hot water connection with pressure range of 20 to 44 PSIG
Each unit shall utilize 1/2 NPSM reverse osmosis water connection with pressure range of 50 to 150 PSIG
Each unit shall utilize 1/4 compressed air connection at 30 PSI
Each unit shall utilize a 120V, 20 amp, GFCI protected receptacle
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Work Station Triple Bay Sinks:
Qty 2, right to left workflow triple bay sinks
Qty 2, left to right workflow triple bay sinks
Each unit must be packaged and delivered to the site in pieces no larger than 132 x 36 x 48 such that they may be handled and will pass through existing openings
Overall maximum unit dimensions 120 W x 28-1/32 D x 52-17/32 T (at max operating height)
Three basins, each with minimum dimensions 30 x 17 x 10"
Stainless Steel Construction
Air and water pistol attachments
Magnetic back splash
Drain system and flex plates
Etched gallon markers in all bays
Must be height adjustable, with minimum working surface height range of 33 to 41
Minimum weight capacity of adjustment lift 562 lbs
Minimum speed of adjustment system 3/8 per second
Must have Pure water faucet
Each unit shall come with a P-trap and utilize a 1-1/2 diameter drain connection.
Each unit shall utilize 1/2 NPSM domestic cold water connection with pressure range of 20 to 44 PSIG
Each unit shall utilize 1/2 NPSM domestic hot water connection with pressure range of 20 to 44 PSIG
Each unit shall utilize 1/2 NPSM reverse osmosis water connection with pressure range of 50 to 150 PSIG
Each unit shall utilize 1/4 compressed air connection at 30 PSI
Each unit shall utilize a 120V, 20 amp, GFCI protected receptacle
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Double Bay Sink:
Qty 1, double bay sink with left to right workflow
Each unit must be packaged and delivered to the site in pieces no larger than 101 x 36 x 48 such that they may be handled and will pass through existing openings
Overall unit dimensions 96 W x 28-1/32 D x 52-17/32 T (at max operating height)
Two basins, each with minimum dimensions 30 x 17 x 10"
Stainless Steel Construction
Air and water pistol attachments
Magnetic back splash
Drain system and flex plates
Etched gallon markers in all bays
Must be height adjustable, with minimum working surface height range of 33 to 41
Minimum weight capacity of adjustment lift 562 lbs
Minimum speed of adjustment system 3/8 per second
Must have pure water faucet
Each unit shall come with a P-trap and utilize a 1-1/2 diameter drain connection.
Each unit shall utilize 1/2 NPSM domestic cold water connection with pressure range of 20 to 44 PSIG
Each unit shall utilize 1/2 NPSM domestic hot water connection with pressure range of 20 to 44 PSIG
Each unit shall utilize 1/2 NPSM reverse osmosis water connection with pressure range of 50 to 150 PSIG
Each unit shall utilize 1/4 compressed air connection at 30 PSI
Each unit shall utilize a 120V, 20 amp, GFCI protected receptacle
Provide Manufacturers User Manuals and Service Manuals
Provide start up and operator training
Prep & Pack Table
QTY 6 Prep and Pack tables
Must be height adjustable
Max dimensions must be 73 W x 40 D x 86 H
Must have lockable casters
Adjustable, Overhead, LED Lighting
CPU Holder
Surface-Mounted Flat Screen Monitor Arm
Multi-function shelving
Each unit shall utilize a 120V, 20 amp receptacle
Provide Manufacturers User Manuals and Service Manuals
Perform installation
Provide start up and operator training