Sources Sought Notice for JSF Hangar Pre-Conditioned Air System Repair at Hangar 75 & Hangar 76, MCAS YUMA, AZ

info alert

Note: There have been new actions to this contract opportunity. To view the most recent action, please click here.

Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information

  • Contract Opportunity Type: Sources Sought (Original)
  • Original Published Date: Oct 26, 2022 10:01 am PDT
  • Original Response Date: Nov 09, 2022 02:00 pm PST
  • Inactive Policy: 15 days after response date
  • Original Inactive Date:
  • Initiative:
    • None

Classification

  • Original Set Aside:
  • Product Service Code: Z2BZ - REPAIR OR ALTERATION OF OTHER AIRFIELD STRUCTURES
  • NAICS Code:
    • 236220 - Commercial and Institutional Building Construction
  • Place of Performance:
    Yuma , AZ 85365
    USA

Description

The goal for this project is to repair the Pre-Conditioned Air (PCA) Systems in two hangars at Marine Corps Air Station, Yuma, Arizona. The project installs and commissions new PCA units in existing hangars. Interested respondents must be able to:

  • Provide standard commercial (cataloged) units that have all of the following features to meet design requirements:
  • Nominal 35-ton cooling capacity, with actual discharge meeting specification air in ambient conditions at or exceeding 111 degrees F dry bulb temperature (see table below for specification air requirements).
  • Minimum 1000 lb/hr purge rate at specification air conditions.
  • Up-blast vertical discharge condenser fans.
  • A pre-cooler upstream of the blower to cool bearings in high ambient temperatures.
  • Provide units with a dual refrigeration circuit system.

A variable frequency drive (VFD) on the second-stage compressor for efficient

Contact Information