Notice of Intent to Award Sole Source to EATON
Note: There have been new actions to this contract opportunity. To view the most recent action, please click here.
General Information
- Contract Opportunity Type: Special Notice (Original)
- Original Published Date: Dec 02, 2024 12:49 pm EST
- Original Response Date:
- Inactive Policy: Manual
- Original Inactive Date: Dec 24, 2024
- Initiative:
- None
Classification
- Original Set Aside:
- Product Service Code:
- NAICS Code:
- Place of Performance:
Description
This is for the purchase of a 'Transient Study'. The objective of the Transient Study is to properly size the snubber on the secondary (11.75 kV) side of each 2250 kVA voltage regulator cyclo-converter transformers feeding the port and starboard rectifiers of an unknown transmitter device. The location of a snubber on the secondary of the transformer is unusual as they are commonly placed on the primary of the transformer to mitigate switching transients created by upstream vacuum circuit breakers (VCBs). The study will determine if a snubber is necessary at this location and, if the study results indicate a snubber is needed, complete specifications for the components shall be provided. If it is determined a snubber is not required on the secondary of the voltage regulator, the application of a snubber on the primary side (4.16 kV) of the voltage regulator shall be examined in a similar way.
This requirement was previously advertised via Request for Info (RFI) NIWC_Pacific_MKTSVY_19D886.