Skip to main content

An official website of the United States government

You have 2 new alerts

FCC HAZELTON, FY25 Water Heating System- PRODUCT ONLY

Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information

  • Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
  • Original Published Date: Jan 14, 2025 12:34 pm EST
  • Original Date Offers Due: Feb 03, 2025 02:00 pm EST
  • Inactive Policy: 15 days after date offers due
  • Original Inactive Date: Feb 18, 2025
  • Initiative:
    • None

Classification

  • Original Set Aside:
  • Product Service Code: 4520 - SPACE AND WATER HEATING EQUIPMENT
  • NAICS Code:
    • 238220 - Plumbing, Heating, and Air-Conditioning Contractors
  • Place of Performance:
    Bruceton Mills , WV 26525
    USA

Description

FCC Hazelton requires a quantity of 4 each indirect plate and frame water heater plus 4 each pumps to accompany the water heaters.  Vendors are required to have active SAM.Gov registration and to provide their UEI. A signed SF1449 must be submitted to be considered received. This requirement is for product ONLY. All quotes and bids are required to be submitted to Andrea Burke, Contract Specialist with FCC Hazelton at Ax2burke@bop.gov  AND HAX-ProcurementProp-S@bop.gov. Quotes must be valid for at least 30 days after close of bids on February 3, 2025 at 2 PM EDT. Specific product requirements below and example spec sheets attached.

Indirect Plate And Frame Water Heater: (4)

Dimensions cannot Exceed: 63” Height Max; 22” Width max; 61” Base Length – MUST FIT THROUGH STANDARD 36” door. Product should not exceed 1200 lbs – Lite Weight Preferred

FEATURES:

ASME DOUBLE WALL HEAT EXCHANGER                                             

• 316L Stainless Steel

• 150 psi Working Pressure

DIGITAL DISPLAY

• DHW Set Point Range 90°F to 180°F

ADVANCED TEMPERATURE CONTROL

MODULATING CONTROL VALVE

SCALE REDUCING PUMP

AUTOMATIC AIR VENT

ASME TEMPERATURE & PRESSURE RELIEF VALVE

• 210°F and 150 psi

ADJUSTABLE HIGH LIMIT

WYE STRAINERS - DOMESTIC PIPING AND

BOILER PIPING

ISOLATION VALVES - DOMESTIC PIPING AND BOILER PIPING

MODBUS COMMUNICATION

WARRANTY

• 5-Year limited warranty/1-Year limited parts

• Warranty for product only without services requirement

SUGGESTED SPECIFICATION

The Indirect Plate and Frame shall be constructed of a 316 stainless steel plate with EPDM gaskets. Maximum unit dimensions shall be: Length ___61_inches, Width ___22___inches and Height __63______ inches.

The Indirect Plate and Frame shall be a double wall. The plate and frame shall be constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the National Board of Boiler and Pressure Vessel Inspectors 

The Indirect Plate and Frame shall have a 150 psi working pressure and be supplied with an ASME temperature and pressure relief valve. Standard equipment shall include Wye Strainers, Isolation Valves, Automatic Air Vent, Scale Reduction Pump, Adjustable High Limit and drain valve

The temperature control shall provide + or – 4 degrees Fahrenheit accuracy with up to a 50% change in load. Setpoint range between 90 and 180 F. Modbus communication shall be standard equipment. The modulating valve shall have a 1000 to 1 turndown. The Indirect Plate and Frame shall be suitable for use with polypropylene glycol, up to 50% concentration. The de-rate associated with the glycol will vary per glycol manufacturer.

Pump: (4) Specifications must meet all below requirements for pump withsystem control and monitoring key

Conditions of Service

Flow: 130 US GPM

Head: 32 ft

Efficiency: 68.6 %

Liquid: Water

Temperature: 60 °C

NPSH required: ft

Pump Data

Specific Gravity: 0.985

Maximum operating pressure: 12 bar

Liquid temperature range: -10 .. 110 °C

Maximum ambient temperature: 40 °C

Flange standard: GF

Pipe connection: GF65

Product number: On request

Motor Data

P1 max: 29 .. 1385 W

Mains frequency: 60 Hz

Enclosure class: X4D

Insulation class: F

Four (4) - Set flanges (2 per set) for line item 0001 tanks
B&G CAST IRON FLANGE PACK, 2" or equivalent

ADDITIONAL INFORMATION: Domestic inlet temp Set point. DHW set point 90 to 180 degrees. GPH for all units together or for each if separated. GPH is for each unit. Each system will supply at minimum hot water to 64-cells, 10-showers, 2-mop closet and 1-staff restroom. Boiler water entering temp 160-180 degrees. Boiler water Leaving temp 120-140 degrees BTU I am looking for specifics on this. -These units are in use 24/7-365 if that helps.

For singled cell showers, 10 to be used at a time with a maximum of up to 128.